Motor start and stop with seal-in

The most used circuit in industry: NO start button, NC stop button, contactor and thermal overload relay.

The simulator is designed for computers (screens 1024 px or wider).

Virtual plant

K1Q0.0F1 · I0.2M 3~0 %

Contactor K1: de-energized. Overload relay: normal. Speed: 0 %

Shown at rest. In the simulator the plant moves according to your program's outputs.

Inputs and outputs

AddressNameDescription
I0.0STARTStart push button (NO)
I0.1STOPStop push button (NC: 1 at rest)
I0.2OVERLOADOverload relay NC contact (driven by the plant: 0 = tripped)
Q0.0K1_MOTORMotor contactor coil

Program

Ladder diagram (LD)

  1. Rung 1 — Start with seal-in. STOP and OVERLOAD are NC contacts in the field: they are examined with NO contacts.

    STARTI0.0K1_MOTORQ0.0STOPI0.1OVERLOADI0.2K1_MOTORQ0.0

Step by step

  1. 1Press ▶ Run (F5). The STOP input is already 1 because the button is NC.
  2. 2Press START: the contactor energizes and the motor speeds up. When you release it, the K1_MOTOR contact branch keeps the circuit closed: that is the seal-in.
  3. 3Press STOP: the input drops to 0, the contact opens and the motor coasts to a stop.
  4. 4In the “Virtual plant” tab, with the motor running, press “Simulate overload”: the thermal relay opens its contact and the motor stops. It cannot start again until the relay is reset.