Star-delta starter with timer

The motor starts in star, with less current, and after a few seconds switches to delta. A timer marks the change and a short pause prevents a short circuit between contactors.

The simulator is designed for computers (screens 1024 px or wider).

Virtual plant

K1Q0.0K2 ⅄Q0.1K3 △Q0.2Connection: Not connected · 0 %Current0 × ratedStarting peak0 × rated

Connection: Not connected. Current: 0 × rated

Shown at rest. In the simulator the plant moves according to your program's outputs.

Inputs and outputs

AddressNameDescription
I0.0STARTStart push button (NO)
I0.1STOPStop push button (NC: 1 at rest)
I0.2OVERLOADOverload relay NC contact (driven by the plant: 0 = tripped)
Q0.0K1_MAINMain contactor
Q0.1K2_STARStar contactor
Q0.2K3_DELTADelta contactor
T0T_STARTime in star (5 s)
T1T_GAPPause between star and delta (100 ms)
M0.0GO_DELTAStar and pause are over: connect delta

Program

Ladder diagram (LD)

  1. Rung 1 — Main contactor with seal-in.

    STARTI0.0K1_MAINQ0.0STOPI0.1OVERLOADI0.2K1_MAINQ0.0
  2. Rung 2 — 5 s in star and a 100 ms pause before delta.

    K1_MAINQ0.0TONT_STARPT T#5sTONT_GAPPT T#100msGO_DELTAM0.0
  3. Rung 3 — Star: until the time is over, interlocked with delta.

    K1_MAINQ0.0T_START0K3_DELTAQ0.2K2_STARQ0.1
  4. Rung 4 — Delta: after the pause, interlocked with star.

    K1_MAINQ0.0GO_DELTAM0.0K2_STARQ0.1K3_DELTAQ0.2

Step by step

  1. 1Press ▶ Run (F5) and press START: K1_MAIN and K2_STAR close. See the starting current in the plant, much lower than with a direct start.
  2. 2After 5 s the T_STAR timer opens K2_STAR. After a 100 ms pause (T_GAP) K3_DELTA closes and the motor reaches its rated speed.
  3. 3The NC contacts of K2 and K3 on each other are an interlock: if both closed together there would be a short circuit. The pause lets the star contact really open before the delta contact closes.
  4. 4Try changing the star time to T#1s: the motor switches to delta at low speed and the current peak goes up.